markchalloner avatar markchalloner commented on August 31, 2024

@msp1974. All good here thanks, same to you.

To answer your questions:

Hot Water Auto Mode (hub is in follow schedule mode)

Normal ...
QUESTION: Should there be a delta value that it has to below target by X before it turns back on to prevent constant on/off around the target temp?

Yes, agreed...

... but what should the delta default to? I did a bit of research into standard (non-smart) hot water cylinder thermostats:

  • The delta is commonly referred to as the temperature differential.
  • This Danfoss document states that the temperature differential is only used for switching on (e.g. a target of 60°C with 10°C differential will switch off at 60°C and on at 50°C):

    General. Most thermostats (not TRVs) switch Off the heat source when rising temperature reaches set point, and
    On when it falls below. Having once switched off, there must then be a slight cooling off - typically less than 1°C -
    before a thermostat can switch on again. This is known as the thermostat’s switching differential or hysteresis.

  • According to a Resideo (licencees of Honeywell Home) support article, the industry standard temperature differential is 10°C:

    The standard temperature differential on the Honeywell Home cylinder thermostats and sensors is 10 degrees. This is an industry standard that has been the case for many years. A wide differential is used to avoid quick cycling of the hot water and to take into account stratification within the hot water cylinder/storage vessel.

  • The wide differential is somewhat backed up out by the specifications of the Drayton HST3 (spec) at 8°C:

    Differential 8°C approximately

  • And Danfoss ATC Cylinder Thermostat at 6-10°C:

    Switching Differential : 6-10

Maybe a user-configurable with a default of 8°C and the wiki updated with the reasoning for this wide differential?

Hot Water Heat Mode (hub is in manual mode)

Normal ...
Override - ??? This is the one I do not get. What is it trying to achieve?

Your description of Continual below summarises this pretty well. I've added more details in the Appendix at the bottom of this reply.

QUESTION: Should the heat mode be more akin to the auto mode in that it has the following function?
Normal ...
Continual - Maintains the water temperature all the time by turning on and off as it reaches target temp/goes below target temp ...

Yes, agreed, Continual is a much nicer term. I would also rename Normal to Once here.

should we have some delta on this?

Yes. It would make sense to apply the same delta across both Auto and Manual modes.

It could be that it should follow the Auto mode settings and call them Normal (keep turning on and off to maintain temp), Once (heat once and then turn off again), but there is a risk that this is non intuative and leaves people with constantly running HW by mistake.

Agreed it would be nice to have consistency between the Auto and Manual modes. We can probably do this by updating the naming. If the naming is consistent then perhaps the default should be too.

I suggest we replace Normal in all cases with something more descriptive and to avoid implying this is the recommended or default state. Continual and Once work well for both Auto and Manual modes. Collecting this all together in your own words:

  • Auto
    • Continual - Follow the schedule on and off but override to off when current temp reaches target temp and then cancel the override to turn back on when current temp is below target temp. Keeps doing this as long as schedule is HW on.
    • Once - Same as above except once target temp reached, uses override to turn off until next scheduled on event.
  • Manual
    • Continual - Maintains the water temperature all the time by turning on and off as it reaches target temp/goes below target temp
    • Once - This works when the hot water is manually turned on (when follow schedule is off) to heat the water to the target temp and then turn off.

Regarding defaults, some considerations (highest priority first):

  • Manual Once mode leaves the user at risk of Legionella bacteria growth if not regularly turned on.
  • Continual mode will cost users more (especially Manual where it could be on all day every day).
  • Manual Once mode leaves the user at risk of not having hot water.
  • Manual Continual (currently Override) mode breaks the usability of the Wiser app: the on and idle state is not visible in the Wiser app and overrides are not cleared when moving to Auto mode in the Wiser app meaning the water could start heating outside of the schedule.
  • Continual mode is how the Wiser app acts.
  • Continual mode is how standard (non-smart) hot water cylinder thermostats act.

I'll also need you to help test when ready if that is ok too?

Yes definitely

Regards

Appendix

Hot Water Heat Mode: Normal vs Override

The Wiser app Hot Water control behaves differently to Room controls. Unlike Rooms, Hot Water doesn't natively have the concept of On and Idle (i.e. not currently heating but can start heating if the temperature drops below X°C). It can only be fully On (and Heating) or Off, stored in the WaterHeatingState field as On or Off. See the app screenshots below for how this is reflected in the UI.

Normal

In Normal mode the Climate's hvac_mode returns HVACMode.HEAT if WaterHeatingState = On and HVACMode.OFF if WaterHeatingState = Off.

✅Pro: The state matches the Wiser app.
⛔Con: Once the temperature rises above the set point the Climate entity will turn fully off and cannot turn itself back on.

Override

In Override mode the missing On and Idle state is tracked in Wiser by abusing the OverrideType field (i.e. is_override). The Climate's hvac_mode returns HVACMode.HEAT if it has an override. As overrides are only used by Wiser in Auto mode, this is a fairly safe hack, though it breaks the usability of the app somewhat (see con below).

✅Pro: Can turn on and off around the temperature set point
⛔Con: The on and idle state is not visible in the Wiser app and overrides are not cleared when moving to Auto mode in the Wiser app meaning the water could start heating outside of the schedule.

Note the override issue could be avoided by either finding another way to track the On and Idle state in Wiser or persisting it it only in Home Assistant.

Wiser App Hot Water control

Screenshot_20240513-220312

Wiser App Room control

Screenshot_20240513-220326

from wiserhomeassistantplatform.

msp1974 avatar msp1974 commented on August 31, 2024

Thanks for your reply. I think i have found a way to not use overrides for managing both continual and once in manual mode and obviously use overrides in auto mode. It needs more testing by me to make sure the logic is right and also handle what happens when advance schedule (which itself uses the same overrides) and boost is used.

I need to think about advance schedule but what do you think of the below for boost?

Should we just have a single boost preset for hw that heats water to target temp once and then cancels. This is the same as turning the water on in manual heat once mode.

Or do we have different time period boosts that maintains the target temp for that period?

from wiserhomeassistantplatform.

Related Issues (20)

Recommend Projects

  • React photo React

    A declarative, efficient, and flexible JavaScript library for building user interfaces.

  • Vue.js photo Vue.js

    🖖 Vue.js is a progressive, incrementally-adoptable JavaScript framework for building UI on the web.

  • Typescript photo Typescript

    TypeScript is a superset of JavaScript that compiles to clean JavaScript output.

  • TensorFlow photo TensorFlow

    An Open Source Machine Learning Framework for Everyone

  • Django photo Django

    The Web framework for perfectionists with deadlines.

  • D3 photo D3

    Bring data to life with SVG, Canvas and HTML. 📊📈🎉

Recommend Topics

  • javascript

    JavaScript (JS) is a lightweight interpreted programming language with first-class functions.

  • web

    Some thing interesting about web. New door for the world.

  • server

    A server is a program made to process requests and deliver data to clients.

  • Machine learning

    Machine learning is a way of modeling and interpreting data that allows a piece of software to respond intelligently.

  • Game

    Some thing interesting about game, make everyone happy.

Recommend Org

  • Facebook photo Facebook

    We are working to build community through open source technology. NB: members must have two-factor auth.

  • Microsoft photo Microsoft

    Open source projects and samples from Microsoft.

  • Google photo Google

    Google ❤️ Open Source for everyone.

  • D3 photo D3

    Data-Driven Documents codes.